OBJECT TO DETERMINE QUANTITY OF WATER REQUIRED TO
PRODUCE CEMENT PASTE OF STANDARD CONSISTENCY
IMPORTANCE This preliminary test
forms base for other tests
OF
TEST
APPARATUS • Vicat Apparatus
• Balance
(capacity 1000
gms accuracy 0.1 gm)
• Gauging Trowel 100-150 mm long
TEMPERATURE • Dry Materials, Water and Laboratory :
27 + 2O C
& HUMIDITY • Relative Humidity in Laboratory :
65 + 5 %
PROCEDURE On
non-porous platform ;
• Prepare cement paste of weighed quantity (300 gm) of cement
mixed with weighed quantity of water (90 gm) using gauging trowel within 3 to 5 minutes before any sign of
setting occurs.
• Immediately fill up mould by vicat apparatus with this paste and
level up. Rest
mould
upon
non-porous plate and shake to remove penetrated air. Level
the top.
• Under plunger rod of vicat apparatus, keep the test block in the
mould together
with non-porous plate. Lower
plunger needle
together to touch top surface of cement
block.
• Release
plunger quickly and allow it to sink in test
block.
• Prepare another sample from same lot by varying water contents and repeat the process
till plunger needle remain embedded in
test specimen 5 to 7 mm from bottom of vicat mould. Note water
content at this stage. The sample is said to be
of standard
consistency at this water content.
CALCULATION Weight of water in sample
Water for standard consistency % =
----------------------------------------- x
100
Weight of dry
cement in sample
|
Sunday, November 25, 2012
CEMENT : DETERMINATION OF CONSISTENCY REFERENCE : IS 4031 – (PART – 4) 1996